Fire Sprinkler Services in Kansas City and Surrounding Areas
Gen X Fire Sprinkler Services offers services and solutions, starting with inspection and testing. If you’ve just purchased a commercial building, an inspection and testing of any existing fire sprinkler system is vital to your safety, the safety of your workers, and the safety of your business. Regular scheduled testing is also a vital way to ensure your system is functioning optimally.
System Inspections
Valves
Are valves in satisfactory condition? Operational? Accessible? Locked, secured, or monitored? Labeled?
System Gauges
Are they in satisfactory condition? Reading normal pressures? Damaged? Greater than 5 years old?
Fire Department Connection
Accessible? Functional? Damaged? Pressure tested from connection to check valve every 5 years, 150 psi for 2 hours with no drop? Signage installed? Outside bell / horn and strobe installed above connection.
Flow Alarms
Should be checked quarterly and at a minimum annually to verify water flow alarm switch is functional with the alarm panel and outside bell.
Fire Sprinkler Heads
Shall be replaced if damaged, painted, or corroded. Fast response heads shall be tested by U.L. Certified laboratory every 20 years and the standard response heads at 50 years of service. Harsh environment heads shall be tested every 5 years or replaced due to the condition of heads. Dry-type heads shall be tested every 10 years.
Main Drain Test
Shall be performed quarterly and compare results with the previous test. If the test indicates a significant drop in pressure an investigation would begin to find out why such as a partially shut valve or an obstruction in the piping.
Dry System Full Trip Test
Once every 3 years the system will be tested with water until it flows to the remote inspector's test valve, other years can be a partial trip test. Check the air maintenance device for automatic operation, air compressor operation, drain low points, low air switch operation.
Fire Pump Test
Weekly tests are required for all fire pumps and flow water thru the test header to test the performance operation of the pump.
Standpipe Systems
Typically found in the egress stairwells, all valves are accessible, flow water every 3 years and pressure test every 5 years.
Backflow Devices
Shall be tested annually to ensure that the potable water is being protected from cross-contamination.
How Often Should I Have A Professional, Such As Gen X Fire Sprinkler Services, Test My System?
The truth is, the frequency of testing will vary depending on a number of factors, including the type of system you have and the regulations in your local area. However, a good rule of thumb is to have your fire sprinkler system tested at least once a year. Regular testing can help ensure that your system is functioning properly and identify any potential issues before they become major headaches.
In addition to annual testing, certain components of your sprinkler system may require more frequent testing. This might include control valves and alarm devices, which are critical to the proper functioning of your system.
Installation and Remodel
Ensure your property is fully protected with Gen X Fire, the trusted fire safety experts serving the Kansas City metropolitan area, including Johnson, Wyandotte, and Jackson counties. Specializing in fire sprinkler installation and remodeling, Gen X Fire delivers top-quality systems that safeguard lives and property by suppressing fires before they spread.
Fire SafeTy and Protection
From design to installation, Gen X Fire ensures your building meets all fire codes, providing peace of mind and compliance with local regulations. Fully licensed and insured, our team brings expertise and reliability to every project. Choose Gen X Fire to enhance your fire safety and protect what matters most.
Specialized Upgrades
When your fire sprinkler system needs an upgrade, Gen X Fire is ready to provide expert remodeling services. We’ll assess your current system and make the necessary modifications to ensure it meets the latest fire safety standards and regulations. Whether your building requires retrofitting or a complete overhaul, our experienced team will deliver a seamless remodel that enhances protection and compliance. Don’t wait—keep your property and occupants safe by updating your fire system with Gen X Fire Sprinkler Services.
Maintenance and Repairs
When you have an existing fire sprinkler system that needs maintenance, you want to be sure the work is done right - and with experience. Gen X Fire Sprinkler Services offers quality repairs and scheduled maintenance to keep your system running efficiently and safely for you, your business, your employees, and your customers.
What Does Maintenance Include?
If you're a business owner, it's important to ensure that your fire sprinkler system is properly maintained and tested to guarantee its functionality during a fire. Skipping this vital step could lead to a shortened life span of your sprinkler system and the possibility that it may not work when needed.
At Gen X Fire Sprinkler Services, we offer a comprehensive maintenance schedule to ensure your fire sprinkler system is always in top working order. Here's what our maintenance schedule includes:
- As needed: We repair and maintain any parts that appear questionable during visual inspections and testing.
- Annually: Once we have inspected your property, we will provide you with a proposal to correct or maintain items on your fire sprinkler system(s).
- Other: May include pipe replacement due to corrosion, flushing out debris from the interior pipe, alarm / supervisory switch replacement, fire sprinkler head replacement, draining low points to prevent freeze damage, air compressor replacement, and backflow device repair work.
Don't risk the safety of your business and occupants. Contact Gen X Fire Sprinkler Services today to ensure your fire sprinkler system is properly maintained and functioning.
The Gen X Difference – We Offer More Options
At Gen X Fire Sprinkler Services we offer several testing schedules including weekly, monthly, quarterly and annual to help you keep in compliance with local authority, state fire marshal requirements and entity’s that oversee safety equipment such as FM Global and Global Risk Management. Gen X Fire Sprinkler Services is a preferred partner to both entities and many others in the safety and fire sprinkler system industry. We also offer inspection and testing services and schedules such as:
- Other frequency Inspection and Testing include: 3 year testing, 5 year internal obstruction investigation, 10 year dry type head test, 20 year fast response head testing, 50 year standard response head testing.
- Backflow device installation, annual testing and repair work.
- Fire pump flow testing and maintenance
- Fire Hydrant flow testing and maintenance
We offer additional resources to our clients including NFPA 25 System Inspections and documented reporting using digital platforms such as Brycer and Inspectpoint.